General specifications | |
---|---|
Signal type | Analog input |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 2 |
Supply | |
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Rated voltage | 20 ... 30 V DC bus powered via Termination Board |
Ripple | within the supply tolerance |
Power dissipation/power consumption | ? 0.98 W / 0.98 W |
Input | |
Connection side | field side |
Connection | SL2: 5a(+), 1a(+), 1b(-), 5b(-) |
RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
Thermocouples | type B, E, J, K, N, R, S, T (IEC584-1:1995) type L (DIN43710:1985) type TXK, TXKH, TXA (P8.585-2001) |
Potentiometer | 0 ... 20 k? (2-wire connection), 0.8 ... 20 k? (3-wire connection) |
Voltage | selectable within the range -100 ... 100 mV |
Input resistance | ? 1 M? (-100 ... 100 mV) |
Output | |
Connection side | control side |
Connection | SL1: 8a(+), 7a(-) |
Output | Analog current output |
Fault indication output | |
Connection | SL1: 6b |
Output type | open collector transistor (internal fault bus) |
Transfer characteristics | |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s |
Indicators/settings | |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches via PACTware |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Conformity | |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529:2001 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
Degree of protection | IP20 |
Mass | approx. 100 g |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Mounting | on Termination Board |
Data for application in connection with hazardous areas | |
EU-Type Examination Certificate | BASEEFA 14 ATEX 0129 X |
Certificate | BASEEFA 14 ATEX 0130 X |
Directive conformity | |
International approvals | |
UL approval | |
IECEx approval | IECEx BAS 14.0071X IECEx BAS 16.0003X |